Data center sizing calculator.
Set your rack count, density and redundancy for an instant, indicative sizing of UPS, cooling, generator, battery and floor area. The numbers update as you move the controls.
Indicative sizing
- IT load
- 100 kW
- UPS capacity
- 174 kVA
- Battery energy
- 19 kWh
- Precision cooling
- 36 TR
- DG set
- 216 kVA
- White-space area
- 690 sq ft
Medium
Indicative only. Assumes PUE ≈ 1.5, 0.9 UPS power factor, 0.8 DG power factor and about 30 sq ft per rack including aisles. Final sizing needs engineering validation against your real equipment and growth plan.
Send this sizing to SNA PowerWhat the numbers mean
These figures put you in the right ballpark for early planning and budgeting.
- UPS (kVA)
- IT load ÷ 0.9 × 1.25 headroom × redundancy factor (N = 1, N+1 ≈ 1.34, 2N = 2)
- Battery (kWh)
- IT load × backup minutes ÷ 60 ÷ 0.9 inverter efficiency
- Cooling (TR)
- IT load ÷ 3.517 × 1.25 margin (1 TR = 3.517 kW of heat)
- DG set (kVA)
- IT load × 1.5 PUE ÷ 0.8 × 1.15 margin, covering IT, cooling and losses
- Floor area
- About 30 sq ft per rack, plus 15–40% for plant and circulation as you scale
Want the reasoning behind these? Read about power sizing, cooling sizing and what N+1 and 2N mean.
Small, medium or large?
| Small | Medium | Large / hyperscale | |
|---|---|---|---|
| Typical use | Server room, edge, SME | Enterprise, colocation floor | Colocation campus, cloud, AI |
| Racks | 1–10 | 10–100 | 100 to several thousand |
| IT load | 5–50 kW | 50 kW – 1 MW | 1 MW – 100+ MW |
| Redundancy | N / N+1 | N+1 | 2N / 2N+1 |
| Cooling | Precision or split AC | CRAC plus containment | Chilled water plus liquid |
| Power | UPS plus small DG | UPS bank plus DG | MV distribution, DG plant |